Below is a structured English technical guide on air source heat pump heating system installation,Key installation specifications, precautions, and maintenance steps are covered for professional reference.
🔧 I. Host Unit Installation Location
Ventilation & Sun Exposure
Install in well-ventilated areas (balcony, roof, ground), ensuring ≥1m clearance for air intake and ≥2m for exhaust outlets. Avoid obstructions to airflow .
Prioritize sunny locations to enhance thermal efficiency and reduce energy consumption .
Load-Bearing & Stability
The base must withstand 2–3 times the unit’s weight. Use a 15–20cm concrete base for ground installation; wall-mounted units require expansion bolts .
Install horizontally with rubber shock pads to minimize operational resonance .
Weather & Drainage Protection
Top-exhaust units need snow hoods to prevent fan blockage .
Defrost drainage pipes must slope toward sewers to avoid ice accumulation and equipment damage .
⚙️ II. Hydraulic System Standards
Water Pump Installation
Orientation: Mount horizontally to prevent bearing wear or motor burnout .
Position: Install on the return-water side (not outlet) to ensure sufficient flow and prevent overheating alarms .
Flow Optimization: Minimize elbows to reduce resistance and maintain pump head .
Freeze Protection & Exhaust
Insulate all outdoor pipes with rubber foam + aluminum tape .
Install automatic air vents at the system’s highest point to prevent airlocks .
Drain water during prolonged inactivity to avoid pipe freezing .
🔌 III. Electrical & Control Systems
Wiring Safety
Position the pump junction box upward to prevent condensation damage .
Ensure voltage matches unit ratings and install leakage protectors .
Temperature Settings
Gradually increase initial water temperature (≤40°C) to prevent system shock .
Coordinate thermostat settings with host parameters to minimize frequent starts/stops .
🛠️ IV. Commissioning & Maintenance
Pre-Debugging Checks
Verify leak-free pipes, secure wiring, and proper end-unit connections .
Test compressor delay protection (3-min startup), abnormal noise, and condensate drainage .
Long-Term Maintenance
Clean hydraulic filters and evaporator fins annually .
Set to low-temperature mode during short absences; drain and power off for extended disuse